MS Company for Cable and Busbar Production/Ltd.

NYIFY / NYIFY-U / NYIFY-R

Dimensions

Nominal
cross-section
Overall diameter
(Approx)
Net Weight
(Approx)
Delivery
Lenght
Conductor DC
Resistance
Current carrying capacity in
mm² mm kg/km m ohm/km In conduit at 20°C A In air at 30°C A
2×1 3,3×9,6 44 100 18,1 12
2×1,5 3,8×12,5 65 100 12,1 18
2×2,5 4,6×14,1 95 100 7,41 26
2×4 6,2×15,5 130 100 4,61 34
3×1 3,3×10,1 65 100 18,1 12
3×1,5 3,8×21,3 100 100 12,1 18
3×2,5 4,6×23,7 145 100 7,41 26
3×4 6,2×25,0 191 100 4,61 34

Additional information

Standard

IEC 60227, IEC 332-1,VDE 0250

Technical Information

Max. Operating Temperature : 70 °C
Max. Short circuit temperature : 160°C
rated Voltage : 300/500 V

Cable Construction

1.Solid or Stranded copper conductor
2.PVC insulation
3.PVC outer sheath

Application

The cable is suitable for nail driving, and is used as the mains, lighting and power cable. It is used in indoor and outdoor areas where there is not much mechanical stress.